| System Voltage | Measure or confirm the nominal voltage between phases and between each phase and neutral. | 120/240 V single-phase; 120/208 V three-phase; 277/480 V three-phase; 347/600 V three-phase. | Choose a panelboard and circuit breakers with voltage ratings equal to or higher than the system voltage. Do not use a breaker below the system voltage. | A 120/240 V residential service requires equipment suitable for a 120/240 V single-phase system. |
| Number of Phases | Identify whether the supply is single-phase or three-phase. | Single-phase: common in homes and small commercial loads. Three-phase: common in commercial and industrial facilities. | Match the board’s phase configuration to the incoming supply and the connected equipment. | A three-phase motor normally requires a three-phase distribution board and a correctly sized multi-pole breaker. |
| Service or Feeder Current | Check the available service rating, feeder rating, and the calculated demand load. | Common panelboard ratings include 100 A, 125 A, 200 A, 400 A, and 600 A. | The board rating should not be lower than the calculated load or the upstream overcurrent protection. The conductors and main breaker must also be properly coordinated. | A calculated demand of 156 A generally requires a system rated at least 200 A, subject to local code and engineering review. |
| Continuous Load | Identify loads expected to operate for three hours or more, such as lighting, heating, or ventilation. | Examples include permanently operating lighting, electric heaters, and data-center cooling equipment. | Apply the continuous-load adjustment required by the applicable electrical code. A common design practice is to size continuous loads at 125%, where required by code. | A 32 A continuous load may require 40 A of calculated capacity when a 125% adjustment applies. |
| Total Connected Load | List the wattage or amperage of all branch circuits and equipment supplied by the board. | Lighting, receptacles, HVAC, pumps, motors, appliances, and specialty equipment. | Use a demand or load calculation rather than simply adding every nameplate value at full capacity. Diversity factors must follow local code and engineering requirements. | A panel with many receptacle circuits may have a lower calculated demand than the sum of every receptacle circuit rating. |
| Branch Circuit Rating | Confirm the expected current of each circuit and the ampacity of its conductors. | Common ratings include 15 A, 20 A, 30 A, 40 A, 50 A, and 60 A. | Select a breaker rating that protects the circuit conductors and equipment. The breaker rating must not exceed the allowable ampacity unless a permitted code exception applies. | A general-purpose receptacle circuit is often 15 A or 20 A, depending on the wiring method and local requirements. |
| Main Breaker Requirement | Determine whether the board needs a main circuit breaker, a main lugs-only configuration, or a separate disconnect. | Main breaker ratings commonly range from 100 A to 600 A in low-voltage distribution equipment. | Use a main breaker when local rules, the installation arrangement, or the available disconnecting means require it. Main lugs-only boards may be suitable when an upstream disconnect is properly provided. | A subpanel supplied from a correctly protected upstream feeder may use main lugs only when permitted by the installation design. |
| Interrupting Rating | Verify the available short-circuit current at the installation point. | Common breaker interrupting ratings include 10 kA, 14 kA, 22 kA, 25 kA, 35 kA, and 65 kA. | The breaker interrupting rating must be equal to or greater than the available fault current. A short-circuit study may be required for larger or complex systems. | If the available fault current is 18 kA, a 10 kA breaker is inadequate; a breaker rated at least 22 kA is typically required. |
| Busbar Rating | Check the current rating and material configuration of the panelboard busbars. | Typical ratings include 100 A, 225 A, 400 A, and 600 A, depending on the equipment design. | The busbar rating must support the maximum permitted supply and distribution current. Verify temperature rating, bracing, and the manufacturer’s approved configuration. | A 225 A board should not be configured to accept a supply exceeding its listed bus rating. |
| Number of Spaces | Count the required single-pole, two-pole, and three-pole breaker positions. | Common capacities include 12, 24, 30, 42, and 54 spaces. | Allow spare spaces for future circuits. Tandem breakers should only be used when the panelboard is specifically listed for them and the installation complies with local requirements. | If 20 spaces are required today, a 24- or 30-space board may provide useful future capacity. |
| Pole Configuration | Determine the number of poles required for each circuit and whether shared-neutral circuits are permitted. | One-pole, two-pole, and three-pole breakers are common in low-voltage systems. | Use multi-pole breakers for multi-phase loads and line-to-line loads where required. The breaker must disconnect all ungrounded conductors simultaneously when required by code. | A 240 V single-phase water heater commonly uses a two-pole breaker. |
| Environment and Enclosure | Assess whether the board will be installed indoors, outdoors, or in a damp, dusty, or corrosive location. | Common enclosure classifications include indoor dry-location enclosures and weather-resistant outdoor enclosures. | Choose an enclosure suitable for the environment, including protection against water, dust, corrosion, and physical damage. Outdoor installations generally require a listed weather-resistant enclosure. | An exterior distribution board needs an enclosure rated for the site’s weather exposure and mounting conditions. |
| Neutral and Grounding Arrangement | Confirm whether the board is used as service equipment or as downstream distribution equipment. | Service equipment typically has a bonded neutral; downstream panels generally keep neutral and equipment grounding conductors separated. | Follow the applicable electrical code and the equipment listing. Do not bond the neutral to the enclosure in a downstream panel unless specifically permitted by the installation design. | A feeder-supplied subpanel normally requires isolated neutral and separate equipment grounding connections. |
| Future Expansion | Estimate likely additions such as HVAC units, electric vehicle charging, solar equipment, or workshop machinery. | Reserve approximately 10%–25% additional spaces when practical; the final allowance depends on the project. | Future capacity must include available bus capacity, feeder capacity, physical space, and the calculated demand load—not space alone. | A commercial renovation may justify a larger board if additional equipment is planned within the next project phase. |