| Insulation system | Dry-type or liquid-immersed | Dry-type designs use solid insulation around the windings; liquid-immersed designs use dielectric liquid for insulation and heat transfer. Confirm the complete insulation system and its rated temperature class on the equipment documentation. | Consider dry-type units where avoiding liquid containment is important. Consider liquid-immersed units where the installation and maintenance plan can accommodate the liquid and its containment requirements. |
| Thermal class | For example, Class F or Class H | Under IEC 60085, Class F and Class H correspond to thermal classes of 155 °C and 180 °C, respectively. These are insulation-system thermal classification values—not recommended ambient temperatures or winding temperature-rise allowances. | Compare the specified insulation class alongside the permitted temperature rise, ambient conditions, loading profile, and manufacturer’s temperature limits. |
| Cooling method | Dry-type: AN or AF Liquid-immersed: ONAN or ONAF | Common IEC cooling designations describe the cooling medium and circulation method: AN is air natural, AF is air forced, ONAN is liquid natural and air natural, and ONAF is liquid natural and air forced. Check the nameplate and documentation for the exact arrangement. | Natural cooling avoids reliance on cooling fans. Forced-air arrangements can support additional cooling capacity when specified, but require suitable fan controls, power, and maintenance. |
| Inverter waveform and harmonics | Transformer designed for the inverter’s actual output | Inverter waveforms and harmonic currents can increase transformer heating and losses. Review the inverter’s voltage waveform, switching characteristics, harmonic spectrum, duty cycle, and any required derating with the transformer designer. | Essential for inverter duty, variable-frequency operation, and applications with significant harmonic content. Do not assume a standard transformer rating alone confirms suitability. |
| Efficiency and losses | No-load loss, load loss, and efficiency at the intended operating point | Ask for guaranteed loss values at the specified voltage, frequency, and reference temperature. No-load loss is present while the transformer is energized; load loss varies with loading. Efficiency depends on operating load, so a single percentage without its test conditions is not enough for comparison. | Compare lifecycle energy use using the expected load profile and hours of operation. Check that competing figures use the same rating, test conditions, and applicable efficiency requirements. |
| Environmental protection | Indoor or outdoor installation; enclosure and site protection | Specify the required enclosure protection for the installation. IP codes under IEC 60529 describe protection against access, solid objects, and water ingress; they do not by themselves establish corrosion resistance, UV resistance, or suitability for every outdoor environment. | For outdoor, dusty, humid, or corrosive locations, define the site conditions and verify the enclosure, coatings, ventilation, and accessories against them. |
| Liquid containment and fire considerations | Liquid type, leak management, and installation controls | For liquid-immersed equipment, identify the dielectric liquid and check applicable fire, spill-containment, and environmental requirements. A dry-type design avoids transformer-liquid leakage, but its fire performance and installation clearances still require verification. | Important in buildings, sensitive sites, and locations near drains or soil. Follow applicable local codes and site risk assessments. |
| Standards and documentation | Applicable transformer and installation requirements | Confirm the applicable standards, rated voltage and frequency, vector group, impedance, temperature-rise limits, cooling designation, routine test results, and guaranteed losses in the technical specification. | Use a common specification checklist when comparing quotations so that ratings, test conditions, and included accessories are consistent. |